Basic Info.
| Model NO. | GW5 |
| Poles Number | 3 |
| Certification | ISO9001-2000, CE, CCC |
| Rated Voltage | 40.5kV |
| Rated Current | 630,1000,1250,1600A |
| Trademark | VACEM |
| Origin | Wenzhou, China |
1.General description
GW5 outdoor disconnect switch is an outdoor H.V. circuit electric appliance in AC 50Hz, rated voltage 40.5kV, 72.5kV and 126kV. It can be used for H.V. circuit making under no-load condition and electric-disconnecting in inspection of H.V. generatrix, appliances as circuit breaker and live H.V. wire. Also, it can be used to make small capacitance of inductive current.
2.Main technical parameter
| Classes | type | Single one weight (kg) | Rated voltage (kV) | Rated current (A) | Isolating switch | Earthing switch | Earthing kinds |
peak withstand current (kA) | Short time withstand current (kA) | peak withstand current(kA) | Short time withstand current(kA) |
| I type | II type | I type | II type |
Common type (anti-pollution type) | VGW5-40.5/ | 92 | 40.5 | 630 | 50 | 20(4s) | 50 | 80 | 20 (4s) | 31.5 (4s) | No earthing, single earthing, double earthing |
| VGW5-40.5 DI-II/ | 94 | 1000 |
| 1250 | 80 | 31.5(4s) |
| 1600 |
3.Structure characteristics
This switch is sorted by earthing-free, single earthing and double earthing. There is a mechanical interlocking between main principal axis and earthing switch. It is equipped with an auxiliary switch.It has manual and automatical operation ways.
Each unipolar equipment is firmed in a base with two post insulators, shaping a V with intersection 50.The main structures as below: base, post insulator. terminal base,contact, earthing switch, earthing static contact and cable terminal.
4.Features
a.Making current freely. Turning flexibility due to rolling bearing, which leading to operational labor saving.
b.It is transmitted by level gear to make the two pillars making current consistently.
c.The opening and closing brake has limited switch to ensure the contactors at the best position.Meanwhile, the handle will be buckled by lock ring after operation.
d.Big clearance between open contacts, sufficient insulating and disconnecting fracture to ensure the operation safety.
e.It has earthing-free, single earthing and double earthing. There is a reliable mechanical inter locking between principal axis and earthing to ensure safety. Users can choose the earthing way accordingly.
f.Operation mechanism can be installed under either pole according to users. The operating effects are same.
5.Product show

6.International fair