Vacuum load switch:FT6 (FZW3A)-12/T630-16 Outdoor AC HV Vacuum load switchgear [Clicked:248] 
FT6 (FZW3A)-12/T630-16 Outdoor AC HV Vacuum load switchgear
General :
FT6 (FZW )-12/T630-16 Outdoor AC HV Vacuum load switchgear£¨hereinafter referred to as load switchgear£© can be used in outdoor three-phase AC power system of rated voltage 10KV and rated frequency 50HZ for opening and closing load current, non-load line and non-load transformer.

Features :
Vertical rotating structure is used for this kind of product, which can avoid the risk of closing automatically.
Vacuum arc-extinguished compartment is equipped in the fully sealed enclosure that operated by high-speed mechanism, and will be not influenced by the outside operation and environment. It can do arc extinguish safety and reliably.
The safety of operation is improved by the connection of vacuum arc-chute and isolating control with no possibility of mis-operation. It has obvious fracture that meets the requirements of disconnecting protection.
The material of the exposed components is made of stainless steel, and has long life service.
The characteristics of the switchgear are neat structure, small volume, less weight and simple, reliable mechanism. It can be operated by two methods: manual operation or dual-purpose operation that is manual or electric. It can be used in the automation of network or the operation of sectional device.The weight of load switchgear: manual or electric operation <=65kg, manual operation<=55kg.

Type Designation

Technical Parameter

NO

 
Item
Unit
Parameter
1
Rated voltage
KV
12
2
Rated frequency
Hz
50
3
Rated current
A
630
4
Rated active load breaking current
A
630
5
Rated closed loop breaking current
A
630
6
5% rated active load breaking current
A
31.5
7
Rated charging breaking current of cable
A
10
8
Rated breaking current of no-load transformer
A
Non-load current of 6000kVA transformer
9
Rated short-time withstand current
KA/s
16/4
10
Rated breaking current of the condenser
A
400
11
Rated peak withstand current
KA
40
12
Rated short-circuit making current
KA
40
13
Rated 1min power frequency withstand voltage (r.m.s) phase to earth, phase-to-phase, vacuum fracture/isolated fracture
KV
42/48
14
Lightning impulse withstand voltage (crest) phase to earth, phase-to-phase, vacuum fracture/isolated fracture
KV
75/85
15
1min wet, withstand voltage earth to earth, phase to phase, isolating point
KV
30/34
16
1min power frequency withstand voltage for isolating point of arc-extinguished compartment
KV
20
17
Mechanical Endurance
Times
2000

Notes for ordering :
Please indicate while ordering:
a. The type, name and quantity;
b. The installation position, top bar or several meters below the top bar and diameter of bar;
c. Operative methods: manual operation or dual-purpose operation that is manual or electric;
d. Please keep contact with us , if you have special order.

 
     
 